For controlling, igniting and monitoring gas burners in continuous operation, in metal housing, plug-in flange plate, adjustable with BCSoft, EC type-tested and certified, AGA approved, certified for systems up to SIL 3 from July 2012 (compliant with PL e).
- Standard version
- T-product, FM and CSA approved
- Safety time on start-up tSA: 10 s
- Safety time in operation tSB: 2 s
- Air valve control
- Mains voltage: 230 V AC, 50/60 Hz
- Ignition transformer TZI 7,5-12/100
- 04 Burner/pilot burner switch-off threshold: 1 mikro A
- 12 Fault lock-out after burner failure in operation
- 15 Flame simulation check in start-up/standby position
- 20 Minimum combustion time tB: as safety time on start-up tSA(2)
- 21 Minimum burner pause time tBP: 0 s
- 23 Burener/pilot burner flame proving period tFS1: 1 s
- 30 Air valve can be controlled externally
- 31 Air valve can be activated externally on start-up
- 32 Air valve in the event of malfunction: can be controlled
- 34 Combustion time during manual mode limited to 5 min.
- Pre-wired for single-electrode operation
- Time between two start-ups: 30 s