For modulating, forced draught burner for gas of unlimited capacity in intermittent or continuous operation
- T-product, FM, CSA and UL approved
- Mains voltage: 120 V AC, 50/60 Hz
- Fan control: 3 A relay
- Valve control: three-point step
- Flame control: ionisation control (continuous or intermittent operation) or UV control (intermittent operation with UVS)
- Digital input function: DGmax. monitoring
- With bottom section
- 11 Minimum burner pause time tBP: 0 s
- 07 Burner start-up attempts: 1
- 22 Switch-on delay time tE: 0 s
- 21 Pre-ignition time tVZ: 0 s
- 12 Safety time 1, burner/pilot burner start-up tSA1: 5 s
- 13 Flame stabilisation time 1, burner/pilot tFS1: 2 s
- 14 Safety time 2, main burner start-up tSA2: 0 s
- 15 Flame stabilisation time 2, main burner tFS2: 2 s
- 29 Controller enable signal delay time tRF: 0 s
- 10 Minimum combustion time tB: 0 s
- 09 Safety time during operation tSB: 2 s
- 27 V2 during burner operation: on
- 08 Behaviour after flame failure during operation: fault lock-out
- 02 Burner switch-off threshold: 1 mikro A
- 17 UVS check: off
- 16 Operating time in manual mode: limited to 5 minutes
- 30 User-defined password
- 04 Air monitoring during pre-purge: off
- 05 Air monitoring during operation: off
- 23 Min. gas pressure monitoring: on
- 24 Digital input function: DGmax. monitoring
- 20 Fan run up time tGV: 0 s
- 25 Valve control: off
- 06 Pre-purge on each start-up: on
- 18 Pre-purge time tPV: 60 s
- 19 Post-purge time tPN: 0 s