For controlling, igniting and monitoring gas burners in continuous operation, in metal housing, plug-in flange plate, adjustable with BCSoft, EC type-tested and certified, AGA approved, certified for systems up to SIL 3 from July 2012 (compliant with PL e).
- Standard version
- Safety time on start-up tSA: 3 s
- Safety time in operation tSB: 1 s
- Mains voltage: 230 V AC, 50/60 Hz
- Ignition transformer TZI 7,5-12/100
- Front film in English with additional stickers in D, F, I, NL, E
- High temperature operation: with continuous operation with ionisation/UVD
- 3 start-up attempts
- 04 Burner/pilot burner switch-off threshold: 1 mikro A
- 12 Fault lock-out after burner failure in operation
- 15 Flame simulation check in start-up/standby position
- 20 Minimum combustion time tB: 3 s
- 21 Minimum burner pause time tBP: 0 s
- 23 Burener/pilot burner flame proving period tFS1: 0 s
- 34 Combustion time during manual mode limited to 5 min.
- Pre-wired for double-electrode operation
- Time between two start-ups: 10 s